- Built-in dual isolators:
– Modern technology supports comprehensive system-andinterface communication
– Allows up to 190 isolators per loop and 30 devices between isolators - Dual input on Model XTRI-D, via a single address
- Integral single-pole, double-throw (SPDT) relay on Model XTRI-R:
– Up to 4 Amps. - Meets Class X (Style 7) survivability requirements
- Low current draw
- Polarity insensitive (in non-isolation mode) via SureWire™ technology:
– Modern technology supports comprehensive system and interface communication - Multi-color light-emitting diode (LED) indicates system status:
– GREEN | AMBER | RED - Mounts in a 4-inch (10.2 cm.) square, 2–¼” (5.7 cm.) deep single-gang or double-gang back box
- Non-obstructive front-end access to programming port and wiring terminals
- Device Programmer | Test Unit programs and verifies address, as well as tests device functionality
- Restriction of Hazardous Substances (RoHS) compliant
- UL864 | UL2572 | UL2017 Listed; CAN/ULC-S527 & CAN/ULC-S576 Listed
– File S24304, Vol. 3
XTRI-S
Single Input Monitor Module with Isolator
Model XTRI-S is one of several intelligent interface modules with Siemens Modular systems. Specifically, it is a single-input interface module can monitor and report the status of a normally open (N.O) or normally closed (N.C) contact. Product is UL864, UL2572 and UL2017 Listed, as well as CAN/ULC-S527 and CAN/ULC-S576 Listed – File S24304, Vol. 3.